The probe is mounted from the top of the vessel and it comprises of a sense electrode which is electrically isolated from the metallic tank by means of a suitable insulator. The sense electrode and the vessel wall serve as the two electrodes of a capacitor with the service material acting as the dielectric. A change in the material level causes a change in the dielectric, which in turn causes the value of this tank capacitor to change. An accurate measurement of this change affords an indirect measure of the level of the material in the tank.
Microprocessor based system for higher degree of reliability and stable operation in noisy environments, made possible with the use of intelligent digital communication between the electronic insert and the evaluation unit
Calibration possible without completely filling and emptying the vessel
Three relays for programming three levels independently or as pump control logic
Three potential free change over relay output contacts
All parameters programmable via Five keys and Five multi-purpose LED displays
Galvanically isolated 4 to 20mA output available for connecting to PLC
Built-in universal power supply for 90 to 260 V AC or for 24 V DC operation.
Extensible probe length from 100 mm up to 3 Meters for Rod probe
Above 3 Meters (Flexible Rope Probe)
W – Weatherproof Probe housing and controller
F – Flameproof enclosure for probe housing suitable for gas group IIA & IIB
Threaded Mounting: 1-1/2”, 2” BSP/NPT
Flanged Mounting: As per specification
Pipe- GI / SS: 200mm – 3000mm
SS / GI Rope above 3 Meters
S4: SS-304
S6: SS-316
MS: Mild Steel Plated
A (Ambient): below 100°C
H1 (High temperature): 100°C – 150°C
H2 (High temperature): above 150°C – 200°C
U: Universal Supply 90 – 265 V AC & 24 V DC
T: Three SPDT relay output (Independently settable & pump control)
A: Analog output (4-20mA, galvanically isolated)
3.5 VA (approx)
Field selectable – Through toggle switches
-50% to 150% multi-purpose
5 digit 0.5” LED
+/- 1-2% of Full Measuring Span
Programmable up to 99 sec
Suitable for continuous monitoring of conductive and non-conductive liquids
Granular material, homogeneous composition having stable dielectric constant
Water based solution
Oil
Slurries
2 LED’s
Red: Alarm, Green: Normal